Cart0Item(s)

Teie ostukorv on tühi

Product was successfully added to your shopping cart.

e-stop rope pull switch XY2CH - 2NC+1NO - flush pushbutton

Tootekood: XY2CH13190H7

Quick Overview

Saadavus: Tellimisel

172,49 € (ilma KM-ta)

Details

Main
range of product
Preventa XY2
product or component type
Latching emergency stop rope pull switch
device short name
XY2CH
housing colour
Red RAL 3000
overvoltage category
Class I conforming to EN/IEC 61140
Class I conforming to NF C 20-030
Complementary
local signalling
Without pilot light
number of cables
1
trigger cable maximum length
30 m
body material
Zamak
cover material
Stainless steel
reset
By flush push-button
contacts type and composition
2 NC + 1 NO
contact operation
Slow-break
trigger cable anchor point
RH or LH side
connections - terminals
Screw clamp terminal, 1 x 0.34...1 x 1 mm²
Screw clamp terminal, 1 x 0.34...2 x 0.75 mm²
tightening torque
0.8…1.2 N.m
cable entry number
3 tapped entry for 1/2" NPT conduit entry
safety level
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508
safety reliability data
B10d = 4000000 conforming to IEC 60947-5-5 value given for a life time of 20 years limited by mechanical or contact wear
marking
CE
mechanical durability
800000 cycles
distance between cable supports
5 m
[Ie] rated operational current
0.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1 appendix A
1.5 A at 240 V, AC-15, B300 conforming to EN/IEC 60947-5-1 appendix A
[Ithe] conventional enclosed thermal current
6 A
[Ui] rated insulation voltage
400 V (pollution degree 3) conforming to EN/IEC 60947-1
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
[Uimp] rated impulse withstand voltage
EN/IEC 60947-1 4 kV
positive opening
With conforming to EN/IEC 60947-5-1
maximum resistance across terminals
25 MOhm conforming to EN/IEC 60255-7 category 3
25 MOhm conforming to NF C 93-050 method A
short-circuit protection
6 A cartridge fuse type gG conforming to EN/IEC 60269
terminals description ISO n°1
(31-32)NC
(21-22)NC
(13-14)NO
net weight
0.865 kg
compatibility code
XY2CH
Environment
standards
EN/IEC 60204-1
CSA C22.2 No 14
Work equipment directive 2009/104/EC
EN/ISO 13850
EN/IEC 60947-5-1
EN/IEC 60947-5-5
UL 508
Machinery directive 2006/42/EC
product certifications
UL category NISD emergency stop devices
CSA
CCC
protective treatment
TC
ambient air temperature for operation
-25…70 °C
ambient air temperature for storage
-40…70 °C
vibration resistance
10 gn (f= 10…150 Hz) conforming to EN/IEC 60068-2-6
shock resistance
50 gn 11 ms conforming to EN/IEC 60068-2-27
IP degree of protection
IP65 conforming to IEC 60529
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free
Yes
RoHS exemption information
Environmental Disclosure
Contractual warranty
Warranty
18 months

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price