Main
range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Resistive load
utilisation category
AC-1
poles description
4P
power pole contact composition
4 NO
[Ue] rated operational voltage
Power circuit <= 300 V DC 25...400 Hz
Power circuit <= 690 V AC
[Ie] rated operational current
125 A 60 °C) <= 440 V AC AC-1 power circuit
control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
110 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
125 A 60 °C power circuit
Irms rated making capacity
1100 A 440 V power circuit IEC 60947
rated breaking capacity
1100 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current
640 A 40 °C - 10 s power circuit
990 A 40 °C - 1 s power circuit
135 A 40 °C - 10 min power circuit
320 A 40 °C - 1 min power circuit
associated fuse rating
200 A gG <= 690 V type 1 power circuit
160 A gG <= 690 V type 2 power circuit
average impedance
0,8 mOhm - Ith 125 A 50 Hz power circuit
[Ui] rated insulation voltage
Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
electrical durability
0,8 Mcycles 125 A AC-1 <= 440 V
power dissipation per pole
12,5 W AC-1
Front cover
Without
mounting support
Plate
Rail
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
GL
LROS (Lloyds register of shipping)
CSA
RINA
UL
DNV
BV
GOST
CCC
connections - terminals
Control circuit screw clamp terminals 2 1…2,5 mm²flexible with cable end
Control circuit screw clamp terminals 1 1…2,5 mm²flexible with cable end
Control circuit screw clamp terminals 1 1…4 mm²flexible without cable end
Control circuit screw clamp terminals 2 1…4 mm²flexible without cable end
Control circuit screw clamp terminals 1 1…4 mm²solid without cable end
Control circuit screw clamp terminals 2 1…4 mm²solid without cable end
Power circuit connector 1 4…50 mm²flexible without cable end
Power circuit connector 2 4…25 mm²flexible without cable end
Power circuit connector 1 4…50 mm²flexible with cable end
Power circuit connector 2 4…16 mm²flexible with cable end
Power circuit connector 1 4…50 mm²solid without cable end
Power circuit connector 2 4…25 mm²solid without cable end
tightening torque
Control circuit 1,2 N.m screw clamp terminals flat Ø 6 mm
Control circuit 1,2 N.m screw clamp terminals Philips No 2
Power circuit 9 N.m connector flat Ø 6 to Ø 8 mm
Power circuit 9 N.m connector hexagonal 4 mm
operating time
20...35 ms closing
6...20 ms opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
mechanical durability
4 Mcycles
maximum operating rate
3600 cyc/h 60 °C
Complementary
coil technology
Without built-in suppressor module
control circuit voltage limits
Operational 0.85...1.1 Uc AC 60 Hz 55 °C)
Drop-out 0.3...0.6 Uc AC 50/60 Hz 55 °C)
Operational 0.8...1.1 Uc AC 50 Hz 55 °C)
inrush power in VA
245 VA 60 Hz 0,75 20 °C)
245 VA 50 Hz 0,75 20 °C)
hold-in power consumption in VA
26 VA 60 Hz 0,3 20 °C)
26 VA 50 Hz 0,3 20 °C)
heat dissipation
6…10 W 50/60 Hz
Environment
IP degree of protection
IP20 front face IEC 60529
protective treatment
TH IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-5…60 °C
ambient air temperature for storage
-60…80 °C
permissible ambient air temperature around the device
-40…70 °C at Uc
operating altitude
3000 m without
fire resistance
850 °C IEC 60695-2-1
flame retardance
V1 UL 94
mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz
Shocks contactor open8 Gn for 11 ms
Vibrations contactor closed3 Gn, 5...300 Hz
Shocks contactor closed10 Gn for 11 ms
height
127 mm
width
96 mm
depth
125 mm
net weight
1,76 kg
Offer Sustainability
Jätkusuutliku pakkumise olek
Green Premium toode
REACh-määrus
Ilma SVHC REACh-ta
Jah
ELi RoHS direktiiv
Mürgiste raskemetallideta
Jah
Elavhõbedavaba
Jah
RoHS eranditeave
Hiina EoHS regulatsioon
Keskkonnaalane avaldus
WEEE
Tootest tuleb Euroopa Liidu turgudel vabaneda vastavuses erijäätmeseadustele ning see ei tohi sattuda olmeprügi sekka.
Contractual warranty
Garantii
18 months

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price