Cart0Item(s)

Teie ostukorv on tühi

Product was successfully added to your shopping cart.
Previous

TeSys SK minikontaktor - 2P (2 NO) - AC-3 - 690 V 5 A - 24 V vahelduvvoolu mähis

Previous

Kontaktor TeSys D | 440V 25A, 400V AC mähis, 3P (3NO), AC-3

Kontaktor TeSys D | 440V 25A, 230V AC 50...60Hz, 4P (4NO), AC-1

Tootekood: LC1DT25P7

Quick Overview

Saadavus: Tellimisel

30,17 € (ilma KM-ta)

Details

Main
range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Resistive load
utilisation category
AC-1
poles description
4P
power pole contact composition
4 NO
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current
25 A 60 °C) <= 440 V AC AC-1 power circuit
control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
230 V AC 50/60 Hz
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
10 A 60 °C signalling circuit
25 A 60 °C power circuit
Irms rated making capacity
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
250 A 440 V power circuit IEC 60947
rated breaking capacity
250 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current
30 A 40 °C - 10 min power circuit
61 A 40 °C - 1 min power circuit
105 A 40 °C - 10 s power circuit
210 A 40 °C - 1 s power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
associated fuse rating
10 A gG signalling circuit IEC 60947-5-1
40 A gG <= 690 V type 1 power circuit
25 A gG <= 690 V type 2 power circuit
average impedance
2,5 mOhm - Ith 25 A 50 Hz power circuit
[Ui] rated insulation voltage
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Power circuit 690 V IEC 60947-4-1
electrical durability
0,8 Mcycles 25 A AC-1 <= 440 V
power dissipation per pole
1,56 W AC-1
Front cover
With
mounting support
Plate
Rail
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
UL
BV
CCC
LROS (Lloyds register of shipping)
DNV
CSA
RINA
GOST
GL
connections - terminals
Control circuit screw clamp terminals 2 1…2,5 mm²flexible with cable end
Control circuit screw clamp terminals 1 1…4 mm²flexible without cable end
Control circuit screw clamp terminals 2 1…4 mm²flexible without cable end
Control circuit screw clamp terminals 1 1…4 mm²flexible with cable end
Control circuit screw clamp terminals 1 1…4 mm²solid without cable end
Control circuit screw clamp terminals 2 1…4 mm²solid without cable end
Power circuit screw clamp terminals 1 1…4 mm²flexible without cable end
Power circuit screw clamp terminals 2 1…4 mm²flexible without cable end
Power circuit screw clamp terminals 1 1…4 mm²flexible with cable end
Power circuit screw clamp terminals 2 1…2,5 mm²flexible with cable end
Power circuit screw clamp terminals 1 1…4 mm²solid without cable end
Power circuit screw clamp terminals 2 1…4 mm²solid without cable end
tightening torque
Control circuit 1,7 N.m screw clamp terminals flat Ø 6 mm
Control circuit 1,7 N.m screw clamp terminals Philips No 2
Power circuit 1,7 N.m screw clamp terminals flat Ø 6 mm
Power circuit 1,7 N.m screw clamp terminals Philips No 2
operating time
4...19 ms opening
12...22 ms closing
safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
mechanical durability
15 Mcycles
maximum operating rate
3600 cyc/h 60 °C
Complementary
coil technology
Without built-in suppressor module
control circuit voltage limits
Drop-out 0.3...0.6 Uc AC 50/60 Hz 60 °C)
Operational 0.8...1.1 Uc AC 50 Hz 60 °C)
Operational 0.85...1.1 Uc AC 60 Hz 60 °C)
inrush power in VA
70 VA 60 Hz 0,75 20 °C)
70 VA 50 Hz 0,75 20 °C)
hold-in power consumption in VA
7,5 VA 60 Hz 0,3 20 °C)
7 VA 50 Hz 0,3 20 °C)
heat dissipation
2…3 W 50/60 Hz
auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
signalling circuit frequency
25...400 Hz
minimum switching current
5 mA signalling circuit
minimum switching voltage
17 V signalling circuit
non-overlap time
1,5 ms on de-energisation between NC and NO contact
1,5 ms on energisation between NC and NO contact
insulation resistance
> 10 MOhm signalling circuit
Environment
IP degree of protection
IP20 front face IEC 60529
protective treatment
TH IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-5…60 °C
ambient air temperature for storage
-60…80 °C
permissible ambient air temperature around the device
-40…70 °C at Uc
operating altitude
3000 m without
fire resistance
850 °C IEC 60695-2-1
flame retardance
V1 UL 94
mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz
Vibrations contactor closed4 Gn, 5...300 Hz
Shocks contactor closed15 Gn for 11 ms
Shocks contactor open10 Gn for 11 ms
height
85 mm
width
45 mm
depth
92 mm
net weight
0,365 kg
Offer Sustainability
Jätkusuutliku pakkumise olek
Green Premium toode
REACh-määrus
Ilma SVHC REACh-ta
Jah
ELi RoHS direktiiv
Mürgiste raskemetallideta
Jah
Elavhõbedavaba
Jah
RoHS eranditeave
Hiina EoHS regulatsioon
Keskkonnaalane avaldus
Ringlusprofiil
WEEE
Tootest tuleb Euroopa Liidu turgudel vabaneda vastavuses erijäätmeseadustele ning see ei tohi sattuda olmeprügi sekka.
Contractual warranty
Garantii
18 months

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price