Cart0Item(s)

Teie ostukorv on tühi

Product was successfully added to your shopping cart.
Previous

Toiteühenduste komplekt, paralleelsed vardad, 3P vahetuskontaktorite kokkupanekuks, LC1D115-D150

Previous

Termilise ülekoormuse releed TeSys LRD | 23...32A, klass 10A

Kontaktor TeSys D | 440V 32A, 24V DC mähis, 4P (2NO + 2NC), AC-1

Tootekood: LC1D188BD

Quick Overview

Saadavus: Tellimisel

57,38 € (ilma KM-ta)

Details

Main
range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Resistive load
utilisation category
AC-1
poles description
4P
power pole contact composition
2 NO + 2 NC
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current
32 A 60 °C) <= 440 V AC AC-1 power circuit
control circuit type
DC standard
[Uc] control circuit voltage
24 V DC
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
10 A 60 °C signalling circuit
32 A 60 °C power circuit
Irms rated making capacity
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
300 A 440 V power circuit IEC 60947
rated breaking capacity
300 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current
145 A 40 °C - 10 s power circuit
240 A 40 °C - 1 s power circuit
40 A 40 °C - 10 min power circuit
84 A 40 °C - 1 min power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
associated fuse rating
10 A gG signalling circuit IEC 60947-5-1
50 A gG <= 690 V type 1 power circuit
35 A gG <= 690 V type 2 power circuit
average impedance
2,5 mOhm - Ith 32 A 50 Hz power circuit
[Ui] rated insulation voltage
Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
electrical durability
1 Mcycles 32 A AC-1 <= 440 V
power dissipation per pole
2,5 W AC-1
Front cover
With
mounting support
Plate
Rail
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
GL
CSA
CCC
RINA
GOST
UL
DNV
BV
LROS (Lloyds register of shipping)
connections - terminals
Control circuit screw clamp terminals 1 1…4 mm²flexible without cable end
Control circuit screw clamp terminals 2 1…4 mm²flexible without cable end
Control circuit screw clamp terminals 1 1…4 mm²flexible with cable end
Control circuit screw clamp terminals 2 1…2,5 mm²flexible with cable end
Control circuit screw clamp terminals 1 1…4 mm²solid without cable end
Control circuit screw clamp terminals 2 1…4 mm²solid without cable end
Power circuit connector 1 2,5…10 mm²flexible without cable end
Power circuit connector 2 2,5…10 mm²flexible without cable end
Power circuit connector 1 2,5…10 mm²flexible with cable end
Power circuit connector 2 2,5…10 mm²flexible with cable end
Power circuit connector 1 2,5…16 mm²solid without cable end
Power circuit connector 2 2,5…16 mm²solid without cable end
tightening torque
Control circuit 1,7 N.m screw clamp terminals flat Ø 6 mm
Control circuit 1,7 N.m screw clamp terminals Philips No 2
Power circuit 1,7 N.m connector flat Ø 6 mm
Power circuit 1,7 N.m connector Philips No 2
operating time
53.55...72.45 ms closing
16...24 ms opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
mechanical durability
30 Mcycles
maximum operating rate
3600 cyc/h 60 °C
Complementary
coil technology
With integral suppression device
control circuit voltage limits
Drop-out 0.1...0.25 Uc DC 60 °C)
Operational 0.7...1.25 Uc DC 60 °C)
time constant
28 ms
inrush power in W
5,4 W 20 °C)
hold-in power consumption in W
5,4 W 20 °C
auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
signalling circuit frequency
25...400 Hz
minimum switching current
5 mA signalling circuit
minimum switching voltage
17 V signalling circuit
non-overlap time
1,5 ms on de-energisation between NC and NO contact
1,5 ms on energisation between NC and NO contact
insulation resistance
> 10 MOhm signalling circuit
Environment
IP degree of protection
IP20 front face IEC 60529
protective treatment
TH IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-5…60 °C
ambient air temperature for storage
-60…80 °C
permissible ambient air temperature around the device
-40…70 °C at Uc
operating altitude
3000 m without
fire resistance
850 °C IEC 60695-2-1
flame retardance
V1 UL 94
mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz
Vibrations contactor closed4 Gn, 5...300 Hz
Shocks contactor open10 Gn for 11 ms
Shocks contactor closed15 Gn for 11 ms
height
91 mm
width
45 mm
depth
107 mm
net weight
0,585 kg
Offer Sustainability
Jätkusuutliku pakkumise olek
Green Premium toode
REACh-määrus
ELi RoHS direktiiv
Elavhõbedavaba
Jah
RoHS eranditeave
Hiina EoHS regulatsioon
Hiina RoHS deklaratsioon
Toode ei kuulu Hiina RoHS sfääri. Ainedeklaratsioon teavitamiseks.
Keskkonnaalane avaldus
Ringlusprofiil
WEEE
Tootest tuleb Euroopa Liidu turgudel vabaneda vastavuses erijäätmeseadustele ning see ei tohi sattuda olmeprügi sekka.
Contractual warranty
Garantii
18 months

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price