Cart0Item(s)

Teie ostukorv on tühi

Product was successfully added to your shopping cart.
Previous

TeSys F - ühenduste komplekt - 3P - ümberlülitus

Previous

Abikontaktplokk, TeSys D, 2NO, eesmine kinnitus, vedruklemmid

Kontaktor TeSys D | 440V 65A, 24V DC standardmähis, 3P (3NO), AC-3

Tootekood: LC1D65A6BD

Quick Overview

Saadavus: Tellimisel

182,26 € (ilma KM-ta)

Details

Main
range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Resistive load
Motor control
utilisation category
AC-1
AC-4
AC-3
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current
80 A 60 °C) <= 440 V AC AC-1 power circuit
65 A 60 °C) <= 440 V AC AC-3 power circuit
motor power kW
11 kW 400 V AC 50/60 Hz AC-4)
18,5 kW 220...230 V AC 50/60 Hz AC-3)
30 kW 380...400 V AC 50/60 Hz AC-3)
37 kW 500 V AC 50/60 Hz AC-3)
37 kW 660...690 V AC 50/60 Hz AC-3)
motor power HP (UL / CSA)
40 hp 460/480 V AC 50/60 Hz 3 phases
5 hp 115 V AC 50/60 Hz 1 phase
10 hp 230/240 V AC 50/60 Hz 1 phase
20 hp 200/208 V AC 50/60 Hz 3 phases
20 hp 230/240 V AC 50/60 Hz 3 phases
50 hp 575/600 V AC 50/60 Hz 3 phases
control circuit type
DC standard
[Uc] control circuit voltage
24 V DC
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
10 A 60 °C signalling circuit
80 A 60 °C power circuit
Irms rated making capacity
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
1000 A 440 V power circuit IEC 60947
rated breaking capacity
1000 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current
520 A 40 °C - 10 s power circuit
900 A 40 °C - 1 s power circuit
110 A 40 °C - 10 min power circuit
260 A 40 °C - 1 min power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
associated fuse rating
10 A gG signalling circuit IEC 60947-5-1
125 A gG <= 690 V type 1 power circuit
125 A gG <= 690 V type 2 power circuit
average impedance
1,5 mOhm - Ith 80 A 50 Hz power circuit
[Ui] rated insulation voltage
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Power circuit 690 V IEC 60947-4-1
electrical durability
0,5 Mcycles 80 A AC-1 <= 440 V
1,45 Mcycles 65 A AC-3 <= 440 V
power dissipation per pole
9,6 W AC-1
6,3 W AC-3
safety cover
With
mounting support
Rail
Plate
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
GOST
CCC
UL
CSA
connections - terminals
Control circuit lugs-ring terminals 8 mm)
Power circuit lugs-ring terminals 16,5 mm)
tightening torque
Control circuit 1,7 N.m lugs-ring terminals flat Ø 6 mm M3.5
Control circuit 1,7 N.m lugs-ring terminals Philips No 2 M3.5
Power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6
operating time
42.5...57.5 ms closing
16...24 ms opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
mechanical durability
10 Mcycles
maximum operating rate
3600 cyc/h 60 °C
Complementary
coil technology
Built-in bidirectional peak limiting diode suppressor
control circuit voltage limits
Drop-out 0.1...0.3 Uc DC 60 °C)
Operational 0.75...1.25 Uc DC 60 °C)
time constant
34 ms
inrush power in W
19 W 20 °C)
hold-in power consumption in W
7,4 W 20 °C
auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
signalling circuit frequency
25...400 Hz
minimum switching current
5 mA signalling circuit
minimum switching voltage
17 V signalling circuit
non-overlap time
1,5 ms on de-energisation between NC and NO contact
1,5 ms on energisation between NC and NO contact
insulation resistance
> 10 MOhm signalling circuit
Environment
IP degree of protection
IP20 front face IEC 60529
protective treatment
TH IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-5…60 °C
ambient air temperature for storage
-60…80 °C
permissible ambient air temperature around the device
-40…70 °C at Uc
operating altitude
3000 m without
fire resistance
850 °C IEC 60695-2-1
flame retardance
V1 UL 94
mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz
Vibrations contactor closed4 Gn, 5...300 Hz
Shocks contactor closed15 Gn for 11 ms
Shocks contactor open10 Gn for 11 ms
height
122 mm
width
55 mm
depth
120 mm
net weight
0,935 kg
Offer Sustainability
Jätkusuutliku pakkumise olek
Green Premium toode
REACh-määrus
Ilma SVHC REACh-ta
Jah
ELi RoHS direktiiv
Mürgiste raskemetallideta
Jah
Elavhõbedavaba
Jah
RoHS eranditeave
Hiina EoHS regulatsioon
Keskkonnaalane avaldus
Ringlusprofiil
WEEE
Tootest tuleb Euroopa Liidu turgudel vabaneda vastavuses erijäätmeseadustele ning see ei tohi sattuda olmeprügi sekka.
Contractual warranty
Garantii
18 months

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price