Tootekood: LC1D256SLS207

Quick Overview

Saadavus: Tellimisel

101,31 € (ilma KM-ta)

Details

Main
range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Resistive load
Motor control
utilisation category
AC-3
AC-1
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
motor power kW
5.5 kW at 220/230 V AC 50 Hz (AC-3)
11 kW at 380/400 V AC 50 Hz (AC-3)
11 kW at 415 V AC 50 Hz (AC-3)
11 kW at 440 V AC 50 Hz (AC-3)
15 kW at 500 V AC 50 Hz (AC-3)
15 kW at 660/690 V AC 50 Hz (AC-3)
[Uc] control circuit voltage
72 V DC
coil type
Low consumption
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
10 A (at 60 °C) for signalling circuit
40 A (at 60 °C) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
450 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity
450 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
240 A 40 °C - 10 s for power circuit
380 A 40 °C - 1 s for power circuit
50 A 40 °C - 10 min for power circuit
120 A 40 °C - 1 min for power circuit
associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
40 A gG at <= 690 V coordination type 2 for power circuit
average impedance
2 mOhm - Ith 40 A 50 Hz for power circuit
[Ui] rated insulation voltage
Power circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
electrical durability
1.65 Mcycles 25 A AC-3 at Ue <= 440 V
1.4 Mcycles 40 A AC-1 at Ue <= 440 V
power dissipation per pole
3.2 W AC-1
1.25 W AC-3
safety cover
With
mounting support
Plate
Rail
standards
EN/IEC 60947-4-1
EN/IEC 60947-5-1
EN 45545 R22 HL3
EN 45545 R26 HL3
DIN 5510-2
product certifications
IEC
CCC
EAC
UA
TR
connections - terminals
Control circuit: lugs-ring terminals (external diameter: 8 mm)
Power circuit: lugs-ring terminals (external diameter: 12 mm)
tightening torque
Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5
Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5
Power circuit: 2.5 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M4
Power circuit: 2.5 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M4
operating time
55...75 ms closing
16...32 ms opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability
30 Mcycles
maximum operating rate
3600 cyc/h 60 °C
Complementary
coil technology
With integral suppression device
control circuit voltage limits
0.1...0.25 Uc 60 °C drop-out DC
0.7...1.25 Uc -40…70 °C operational DC
time constant
37 ms
inrush power in W
4 W at 20 °C
hold-in power consumption in W
4 W at 20 °C
auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency
25...400 Hz
minimum switching current
5 mA for signalling circuit
minimum switching voltage
17 V for signalling circuit
non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance
> 10 MOhm for signalling circuit
Environment
IP degree of protection
IP20 front face conforming to IEC 60529
protective treatment
TH conforming to IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-25…60 °C
ambient air temperature for storage
-60…80 °C
permissible ambient air temperature around the device
-40…70 °C at Uc
operating altitude
3000 m without
fire resistance
850 °C conforming to IEC 60695-2-1
flame retardance
V0 conforming to UL 94
mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 8 Gn for 11 ms
height
85 mm
width
45 mm
depth
101 mm
net weight
0.37 kg
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
REACh free of SVHC
Yes
EU RoHS Directive
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price