utilisation category | AC-3AC-4AC-1 | |
---|
poles description | 3P | |
---|
power pole contact composition | 3 NO | |
---|
[Ue] rated operational voltage | Power circuit 690 V AC 50/60 HzSignalling circuit <= 690 V AC 50/60 Hz | |
---|
[Ie] rated operational current | 20 A 50 °C) <= 440 V AC AC-1 power circuit9 A<= 440 V AC AC-3 power circuit16 A 70 °C) 690 V AC AC-1 power circuit | |
---|
control circuit type | AC 50/60 Hz | |
---|
[Uc] control circuit voltage | 24 V AC 50/60 Hz | |
---|
motor power kW | 2,2 kW 220...230 V AC 50/60 Hz AC-34 kW 380...415 V AC 50/60 Hz AC-34 kW 440 V AC 50/60 Hz AC-34 kW 480 V AC 50/60 Hz AC-34 kW 500...600 V AC 50/60 Hz AC-34 kW 660...690 V AC 50/60 Hz AC-32,2 kW 400 V AC 50/60 Hz AC-4 | |
---|
auxiliary contact composition | 1 NC | |
---|
[Uimp] rated impulse withstand voltage | 8 kV | |
---|
overvoltage category | III | |
---|
[Ith] conventional free air thermal current | 20 A 50 °C power circuit10 A 50 °C signalling circuit | |
---|
Irms rated making capacity | 110 A AC power circuit NF C 63-110110 A AC power circuit IEC 60947110 A AC signalling circuit IEC 60947 | |
---|
rated breaking capacity | 110 A 415 V IEC 60947110 A 440 V IEC 6094780 A 500 V IEC 60947110 A 220...230 V IEC 60947110 A 380...400 V IEC 6094770 A 660...690 V IEC 60947 | |
---|
[Icw] rated short-time withstand current | 90 A 50 °C - 1 s power circuit85 A 50 °C - 5 s power circuit80 A 50 °C - 10 s power circuit60 A 50 °C - 30 s power circuit45 A 50 °C - 1 min power circuit40 A 50 °C - 3 min power circuit20 A 50 °C - >= 15 min power circuit80 A - 1 s signalling circuit90 A - 500 ms signalling circuit110 A - 100 ms signalling circuit | |
---|
associated fuse rating | 25 A gG <= 440 V power circuit25 A aM power circuit10 A gG signalling circuit IEC 6094710 A gG signalling circuit VDE 0660 | |
---|
average impedance | 3 mOhm - Ith 20 A 50 Hz power circuit | |
---|
[Ui] rated insulation voltage | Power circuit 600 V UL 508Power circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-5-1Signalling circuit 600 V UL 508Power circuit 600 V CSA C22.2 No 14Signalling circuit 600 V CSA C22.2 No 14 | |
---|
insulation resistance | > 10 MOhm signalling circuit | |
---|
inrush power in VA | 30 VA 20 °C) | |
---|
hold-in power consumption in VA | 4,5 VA 20 °C) | |
---|
heat dissipation | 1,3 W | |
---|
control circuit voltage limits | Operational 0.8...1.15 Uc 50 °C)Drop-out 0.2...0.75 Uc 50 °C) | |
---|
connections - terminals | screw clamp terminals 1 1,5…4 mm²solid screw clamp terminals 1 0,75…4 mm²flexible without cable end screw clamp terminals 1 0,34…2,5 mm²flexible with cable end screw clamp terminals 2 1,5…4 mm²solid screw clamp terminals 2 0,75…4 mm²flexible without cable end screw clamp terminals 2 0,34…1,5 mm²flexible with cable end | |
---|
maximum operating rate | 3600 cyc/h | |
---|
auxiliary contacts type | Instantaneous 1 NC | |
---|
signalling circuit frequency | <= 400 Hz | |
---|
minimum switching current | 5 mA signalling circuit | |
---|
minimum switching voltage | 17 V signalling circuit | |
---|
mounting support | PlateRail | |
---|
tightening torque | 1,3 N.m screw clamp terminals Philips No 2 1,3 N.m screw clamp terminals flat Ø 6 mm | |
---|
operating time | 10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing | |
---|
safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 | |
---|
non overlap distance | 0,5 mm | |
---|
mechanical durability | 10 Mcycles | |
---|
electrical durability | 0,18 Mcycles 20 A AC-1 <= 440 V1,3 Mcycles 9 A AC-3 <= 440 V | |
---|
mechanical robustness | Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6 | |
---|
height | 58 mm | |
---|
depth | 57 mm | |
---|