Cart0Item(s)

Teie ostukorv on tühi

Product was successfully added to your shopping cart.
Previous

Kontaktori mähis TeSys D — LX1D6 | 400V AC, 50...60Hz, 80 ja 95A kontaktori jaoks

Previous

Kontaktor TeSys K | 440V 20A, 120V AC, 4P (2NO + 2NC), AC-1

TeSys K tagurduskontaktor - 3P - AC-3 <= 440 V 9 A - 1 NC - 127 V AC spiraal

Tootekood: LC2K0901FC7

Quick Overview

Saadavus: Ei saa enam tellida

68,96 € (ilma KM-ta)

Details

Main
range
TeSys
product name
TeSys K
product or component type
Reversing contactor
device short name
LC2K
device application
Control
contactor application
Resistive load
Motor control
utilisation category
AC-1
AC-3
AC-4
device presentation
Preassembled with reversing power busbar
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit 690 V AC 50/60 Hz
Signalling circuit <= 690 V AC 50/60 Hz
[Ie] rated operational current
20 A 50 °C) <= 440 V AC AC-1 power circuit
16 A 70 °C) 690 V AC AC-1 power circuit
9 A<= 440 V AC AC-3 power circuit
motor power kW
2,2 kW 220...230 V AC 50/60 Hz
4 kW 380...415 V AC 50/60 Hz
4 kW 440 V AC 50/60 Hz
4 kW 480 V AC 50/60 Hz
4 kW 500...600 V AC 50/60 Hz
4 kW 660...690 V AC 50/60 Hz
control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
127 V AC 50/60 Hz
auxiliary contact composition
1 NC
[Uimp] rated impulse withstand voltage
8 kV
overvoltage category
III
[Ith] conventional free air thermal current
20 A 50 °C power circuit
10 A 50 °C signalling circuit
Irms rated making capacity
110 A AC power circuit NF C 63-110
110 A AC power circuit IEC 60947
110 A AC signalling circuit IEC 60947
rated breaking capacity
110 A 415 V IEC 60947
110 A 440 V IEC 60947
80 A 500 V IEC 60947
110 A 220...230 V IEC 60947
110 A 380...400 V IEC 60947
70 A 660...690 V IEC 60947
[Icw] rated short-time withstand current
90 A 50 °C - 1 s power circuit
85 A 50 °C - 5 s power circuit
80 A 50 °C - 10 s power circuit
60 A 50 °C - 30 s power circuit
45 A 50 °C - 1 min power circuit
40 A 50 °C - 3 min power circuit
80 A - 1 s signalling circuit
90 A - 500 ms signalling circuit
110 A - 100 ms signalling circuit
20 A 50 °C - >= 15 min power circuit
associated fuse rating
25 A gG <= 440 V power circuit
25 A aM power circuit
10 A gG signalling circuit IEC 60947
10 A gG signalling circuit VDE 0660
average impedance
3 mOhm - Ith 20 A 50 Hz power circuit
[Ui] rated insulation voltage
Power circuit 600 V UL 508
Power circuit 690 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-5-1
Signalling circuit 600 V UL 508
Power circuit 600 V CSA C22.2 No 14
Signalling circuit 600 V CSA C22.2 No 14
electrical durability
0,18 Mcycles 20 A AC-1 <= 440 V
1,3 Mcycles 9 A AC-3 <= 440 V
interlocking type
Mechanical
mounting support
Rail
Plate
standards
BS 5424
IEC 60947
VDE 0660
NF C 63-110
product certifications
UL
CSA
connections - terminals
screw clamp terminals 1 1,5…4 mm²solid
screw clamp terminals 1 0,75…4 mm²flexible without cable end
screw clamp terminals 1 0,34…2,5 mm²flexible with cable end
screw clamp terminals 2 1,5…4 mm²solid
screw clamp terminals 2 0,75…4 mm²flexible without cable end
screw clamp terminals 2 0,34…1,5 mm²flexible with cable end
tightening torque
1,3 N.m screw clamp terminals Philips No 2
1,3 N.m screw clamp terminals flat Ø 6 mm
operating time
10...20 ms coil energisation and NO closing
10...20 ms coil de-energisation and NO opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
mechanical durability
5 Mcycles
maximum operating rate
3600 cyc/h
Complementary
control circuit voltage limits
Operational 0.8...1.15 Uc 50 °C)
Drop-out 0.2...0.75 Uc 50 °C)
inrush power in VA
30 VA 20 °C)
hold-in power consumption in VA
4,5 VA 20 °C)
heat dissipation
1,3 W
auxiliary contacts type
Instantaneous 1 NC
signalling circuit frequency
<= 400 Hz
minimum switching current
5 mA signalling circuit
minimum switching voltage
17 V signalling circuit
non overlap distance
0,5 mm
insulation resistance
> 10 MOhm signalling circuit
Environment
IP degree of protection
IP20 VDE 0106
protective treatment
TC IEC 60068
TC DIN 50016
ambient air temperature for operation
-25…50 °C
ambient air temperature for storage
-50…80 °C
operating altitude
2000 m without
flame retardance
V1 UL 94
Requirement 2 NF F 16-101
Requirement 2 NF F 16-102
mechanical robustness
Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
height
58 mm
width
90 mm
depth
57 mm
net weight
0,39 kg
Offer Sustainability
Jätkusuutliku pakkumise olek
Green Premium toode
REACh-määrus
Ilma SVHC REACh-ta
Jah
ELi RoHS direktiiv
Elavhõbedavaba
Jah
RoHS eranditeave
Hiina EoHS regulatsioon
Hiina RoHS deklaratsioon
Toode ei kuulu Hiina RoHS sfääri. Ainedeklaratsioon teavitamiseks.
Keskkonnaalane avaldus
Ringlusprofiil
WEEE
Tootest tuleb Euroopa Liidu turgudel vabaneda vastavuses erijäätmeseadustele ning see ei tohi sattuda olmeprügi sekka.
Contractual warranty
Garantii
18 months

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price