| local display |  Without  |  | 
|---|
| number or control scheme lines |  0…240 ladder0…500 FBD  |  | 
|---|
| cycle time |  6…90 ms  |  | 
|---|
| backup time |  10 years 25 °C  |  | 
|---|
| clock drift |  12 min/year 0…55 °C6 s/month 25 °C  |  | 
|---|
| checks |  Program memory on each power up  |  | 
|---|
| [Us] rated supply voltage |  24 V DC  |  | 
|---|
| supply voltage limits |  19,2…30 V  |  | 
|---|
| maximum supply current |  100 mA without extension)  |  | 
|---|
| power dissipation in W |  6 W without extension  |  | 
|---|
| reverse polarity protection |  With  |  | 
|---|
| discrete input number |  12 EN/IEC 61131-2 type 1  |  | 
|---|
| discrete input type |  Resistive  |  | 
|---|
| discrete input voltage |  24 V DC  |  | 
|---|
| discrete input current |  4 mA  |  | 
|---|
| counting frequency |  1 kHz discrete input  |  | 
|---|
| voltage state 1 guaranteed |  >= 15 V I1...IA and IH...IR discrete input circuit>= 15 V IB...IG used as discrete input circuit  |  | 
|---|
| voltage state 0 guaranteed | <= 5 V I1...IA and IH...IR discrete input circuit<= 5 V IB...IG used as discrete input circuit  |  | 
|---|
| current state 1 guaranteed |  >= 1.2 mA IB...IG used as discrete input circuit)>= 2.2 mA I1...IA and IH...IR discrete input circuit)  |  | 
|---|
| current state 0 guaranteed | <= 0.5 mA IB...IG used as discrete input circuit)<= 0.75 mA I1...IA and IH...IR discrete input circuit)  |  | 
|---|
| input compatibility |  3-wire proximity sensors PNP discrete input  |  | 
|---|
| analogue input number |  6  |  | 
|---|
| analogue input type |  Common mode  |  | 
|---|
| analogue input range |  0...10 V0...24 V  |  | 
|---|
| maximum permissible voltage |  30 V analogue input circuit  |  | 
|---|
| analogue input resolution |  8 bits  |  | 
|---|
| LSB value |  39 mV analogue input circuit  |  | 
|---|
| conversion time |  Smart relay cycle time analogue input circuit  |  | 
|---|
| conversion error |  +/- 5 % 25 °C analogue input circuit+/- 6.2 % 55 °C analogue input circuit  |  | 
|---|
| repeat accuracy |  +/- 2 % 55 °C analogue input circuit  |  | 
|---|
| operating distance |  10 m between stations, with screened cable (sensor not isolated) analogue input circuit  |  | 
|---|
| input impedance |  12 kOhm IB...IG used as analogue input circuit12 kOhm IB...IG used as discrete input circuit7.4 kOhm I1...IA and IH...IR discrete input circuit  |  | 
|---|
| number of outputs |  8 relay  |  | 
|---|
| output voltage limits |  24...250 V AC relay output)5...30 V DC relay output)  |  | 
|---|
| contacts type and composition |  NO relay output  |  | 
|---|
| output thermal current |  8 A for all 8 outputs relay output  |  | 
|---|
| electrical durability |  AC-12 500000 cycles 230 V, 1,5 A relay output EN/IEC 60947-5-1AC-15 500000 cycles 230 V, 0,9 A relay output EN/IEC 60947-5-1DC-12 500000 cycles 24 V, 1,5 A relay output EN/IEC 60947-5-1DC-13 500000 cycles 24 V, 0,6 A relay output EN/IEC 60947-5-1  |  | 
|---|
| switching capacity in mA |  >= 10 mA 12 V relay output)  |  | 
|---|
| operating rate in Hz |  0,1 Hz at Ie)relay output10 Hz no load)relay output  |  | 
|---|
| mechanical durability |  10000000 cycles relay output  |  | 
|---|
| [Uimp] rated impulse withstand voltage |  4 kV EN/IEC 60947-1 and EN/IEC 60664-1  |  | 
|---|
| clock |  With  |  | 
|---|
| response time |  10 ms from state 0 to state 1)relay output5 ms from state 1 to state 0)relay output  |  | 
|---|
| connections - terminals |  Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solidScrew terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solidScrew terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable endScrew terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solidScrew terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end  |  | 
|---|
| tightening torque |  0,5 N.m  |  | 
|---|
| overvoltage category |  III EN/IEC 60664-1  |  | 
|---|
| net weight |  0,35 kg  |  | 
|---|