local display | Without | |
---|
number or control scheme lines | 0…240 ladder0…500 FBD | |
---|
cycle time | 6…90 ms | |
---|
backup time | 10 years 25 °C | |
---|
clock drift | 12 min/year 0…55 °C6 s/month 25 °C | |
---|
checks | Program memory on each power up | |
---|
[Us] rated supply voltage | 24 V DC | |
---|
supply voltage limits | 19,2…30 V | |
---|
maximum supply current | 100 mA without extension) | |
---|
power dissipation in W | 6 W without extension | |
---|
reverse polarity protection | With | |
---|
discrete input number | 12 EN/IEC 61131-2 type 1 | |
---|
discrete input type | Resistive | |
---|
discrete input voltage | 24 V DC | |
---|
discrete input current | 4 mA | |
---|
counting frequency | 1 kHz discrete input | |
---|
voltage state 1 guaranteed | >= 15 V I1...IA and IH...IR discrete input circuit>= 15 V IB...IG used as discrete input circuit | |
---|
voltage state 0 guaranteed | <= 5 V I1...IA and IH...IR discrete input circuit<= 5 V IB...IG used as discrete input circuit | |
---|
current state 1 guaranteed | >= 1.2 mA IB...IG used as discrete input circuit)>= 2.2 mA I1...IA and IH...IR discrete input circuit) | |
---|
current state 0 guaranteed | <= 0.5 mA IB...IG used as discrete input circuit)<= 0.75 mA I1...IA and IH...IR discrete input circuit) | |
---|
input compatibility | 3-wire proximity sensors PNP discrete input | |
---|
analogue input number | 6 | |
---|
analogue input type | Common mode | |
---|
analogue input range | 0...10 V0...24 V | |
---|
maximum permissible voltage | 30 V analogue input circuit | |
---|
analogue input resolution | 8 bits | |
---|
LSB value | 39 mV analogue input circuit | |
---|
conversion time | Smart relay cycle time analogue input circuit | |
---|
conversion error | +/- 5 % 25 °C analogue input circuit+/- 6.2 % 55 °C analogue input circuit | |
---|
repeat accuracy | +/- 2 % 55 °C analogue input circuit | |
---|
operating distance | 10 m between stations, with screened cable (sensor not isolated) analogue input circuit | |
---|
input impedance | 12 kOhm IB...IG used as analogue input circuit12 kOhm IB...IG used as discrete input circuit7.4 kOhm I1...IA and IH...IR discrete input circuit | |
---|
number of outputs | 8 relay | |
---|
output voltage limits | 24...250 V AC relay output)5...30 V DC relay output) | |
---|
contacts type and composition | NO relay output | |
---|
output thermal current | 8 A for all 8 outputs relay output | |
---|
electrical durability | AC-12 500000 cycles 230 V, 1,5 A relay output EN/IEC 60947-5-1AC-15 500000 cycles 230 V, 0,9 A relay output EN/IEC 60947-5-1DC-12 500000 cycles 24 V, 1,5 A relay output EN/IEC 60947-5-1DC-13 500000 cycles 24 V, 0,6 A relay output EN/IEC 60947-5-1 | |
---|
switching capacity in mA | >= 10 mA 12 V relay output) | |
---|
operating rate in Hz | 0,1 Hz at Ie)relay output10 Hz no load)relay output | |
---|
mechanical durability | 10000000 cycles relay output | |
---|
[Uimp] rated impulse withstand voltage | 4 kV EN/IEC 60947-1 and EN/IEC 60664-1 | |
---|
clock | With | |
---|
response time | 10 ms from state 0 to state 1)relay output5 ms from state 1 to state 0)relay output | |
---|
connections - terminals | Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solidScrew terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solidScrew terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable endScrew terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solidScrew terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end | |
---|
tightening torque | 0,5 N.m | |
---|
overvoltage category | III EN/IEC 60664-1 | |
---|
net weight | 0,35 kg | |
---|