Resistance to electrostatic discharge (air discharge), 8 kV, conforming to IEC 61000-4-2Resistance to electrostatic discharge (contact discharge), 4 kV, conforming to IEC 61000-4-2Resistance to radiated electromagnetic fields (80 MHz...3 GHz), 10 V/m, conforming to IEC 61000-4-3Power supply: resistance to fast transient (5...100 kHz), 2 kV, conforming to IEC 61000-4-4Input/output: resistance to fast transient, 1 kV, conforming to IEC 61000-4-4Communication bus: resistance to fast transient, 1 kV, conforming to IEC 61000-4-4Conducted EMC (0.15...80 MHz), 10 V, conforming to IEC 61000-4-6Immunity to magnetic fields at network frequency, 30 A/m, conforming to IEC 61000-4-8Radiated emission (30...1000 MHz), class A, conforming to IEC 61131-3 Ed.3Conducted emission (0.15...30 MHz), class A, conforming to IEC 61131-2 |