Main
range of product
Modicon M221
product or component type
Analogue input cartridge
product compatibility
Modicon M221C
analogue input number
2
Complementary
analogue input type
thermocouple - 200...1000 °C with thermocouple J
thermocouple - 200...1300 °C with thermocouple K
thermocouple 0...1760 °C with thermocouple R
thermocouple 0...1760 °C with thermocouple S
thermocouple 0...1820 °C with thermocouple B
thermocouple - 200...400 °C with thermocouple T
thermocouple - 200...1300 °C with thermocouple N
thermocouple - 200...800 °C with thermocouple E
thermocouple 0...2315 °C with thermocouple C
Ni 100/Ni 1000 temperature probe - 60...180 °C
Pt 100 temperature probe - 200...850 °C
Pt 1000 temperature probe - 200...600 °C
analogue input resolution
14 bits
LSB value
0.1 °C
sampling duration
125 ms, analogue input type: thermocouple
250 ms, analogue input type: temperature probe
absolute accuracy error
+/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe
+/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C
+/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C
+/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C
+/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C
+/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C
+/- 6 °C at 25 °C for thermocouple R, S 0...200 °C
+/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C
+/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C
temperature drift
+/- 0.02 %FS/°C
repeat accuracy
+/- 0.5 %FS
non-linearity
+/- 0.01 %FS
cross talk
<= 1 LSB
type of cable
Twisted shielded pairs cable
electrical connection
3 x 1.5 mm² 2 screw terminal blocks with pitch 3.81 mm adjustment for inputs
maximum cable distance between devices
Twisted shielded pairs cable: <30 m for input
insulation
Non-insulated between analogue input and internal logic
height
41 mm
depth
15 mm
width
35 mm
net weight
0.015 kg
input impedance
>= 1 MOhm
Environment
immunity to microbreaks
10 ms
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price