module network TM4 4 Ethernet switchs

Tootekood: TM4ES4

Quick Overview

Saadavus: Tellimisel

175,34 € (ilma KM-ta)

Details

Main
product or component type
Ethernet unmanaged switch
Complementary
range compatibility
Modicon M251
Modicon M241
product compatibility
Modicon M241 logic controller
Modicon M251 logic controller
current consumption
360 mA at 5 V DC for communication bus
integrated connection type
Ethernet: 4 RJ45 connector
transmission rate
10/100 Mbit/s
port Ethernet
10BASE-T/100BASE-TX - 4 port(s) copper cable
web services
Web server
communication service
Modbus TCP server
Modbus TCP slave device
FTP
NGVL
Monitoring
IEC VAR ACCESS
Programming
SNMP
Modbus TCP client
Downloading
Updating firmware
Ethernet/IP slave device
DHCP client
maximum number of connections
8 Modbus server
16 Ethernet/IP device
communication port protocol
Ethernet IP/Modbus TCP
TCP (Transmission Control Protocol)
UDP (User Datagram Protocol)
SNMP
redundancy
No
local signalling
1 LED (green)PWR:
1 LED per channel (green/yellow)Ethernet link:
1 LED per channel (green)Ethernet port activity:
electrical connection
RJ45 4 connectors for connecting Ethernet network
Screw connector terminal for connecting the functional ground
marking
CE
surge withstand
1 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5
2 kV relay output common mode conforming to EN/IEC 61000-4-5
1 kV I/O common mode conforming to EN/IEC 61000-4-5
1 kV shielded cable common mode conforming to EN/IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5
1 kV relay output differential mode conforming to EN/IEC 61000-4-5
0.5 kV I/O differential mode conforming to EN/IEC 61000-4-5
mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
width
25 mm
height
90 mm
depth
90 mm
net weight
0.125 kg
Environment
standards
UL 508
EN/IEC 61131-2
product certifications
CULus
C-Tick
resistance to electrostatic discharge
8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to Marine specification (LR, ABS, DNV, GL)
6 kV on contact conforming to Marine specification (LR, ABS, DNV, GL)
resistance to electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
resistance to fast transients
2 kV (power lines) conforming to EN/IEC 61000-4-4
2 kV (relay output) conforming to EN/IEC 61000-4-4
1.5 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (Ethernet line) conforming to EN/IEC 61000-4-4
1 kV (serial link) conforming to EN/IEC 61000-4-4
resistance to conducted disturbances
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
electromagnetic emission
Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A at 30…230 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 60...54 dBμV/m QP at 30…100 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions - test level: 24 dBμV/m QP at 156…165 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A at 230…1000 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 80...50 dμV/m QP at 150…30000 kHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions - test level: 54 dBμV/m QP at 100…2000 MHz conforming to Marine specification (LR, ABS, DNV, GL)
ambient air temperature for operation
-10…55 °C horizontal installation
-10…50 °C vertical installation
ambient air temperature for storage
-25…70 °C
relative humidity
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
IP degree of protection
IP20 with protective cover in place
pollution degree
2
operating altitude
0...2000 m
storage altitude
0…3000 m
vibration resistance
1 mm at 5…13.2 Hz on symmetrical rail
3 gn at 8.7…150 Hz on symmetrical rail
1 mm at 5…13.2 Hz on panel mounting
0.7 gn at 13.2…100 Hz on panel mounting
shock resistance
15 gn for 11 ms
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price