product destination | asynchronous motors synchronous motors | |
---|
assembly style | In floor-standing enclosure compact version | |
---|
cable entry | Bottom | |
---|
type of cooling | Forced convection | |
---|
[Us] rated supply voltage | 380...415 V - 10...6 % | |
---|
supply frequency | 50...60 Hz +/- 5 % | |
---|
network number of phases | 3 phases | |
---|
overvoltage category | III | |
---|
synchronous motor control profile | Permanent magnet motor | |
---|
output voltage | <= power supply voltage | |
---|
permissible temporary current boost | 1.2 x In 60 s normal duty)1.5 x In 60 s heavy duty) | |
---|
nominal switching frequency | 2.5 kHz | |
---|
switching frequency | 2...8 kHz adjustable with derating factor | |
---|
speed drive output frequency | 0,1…500 Hz | |
---|
motor power kW | 315 kW normal duty250 kW heavy duty | |
---|
continuous output current | 590 A 2.5 kHz normal duty477 A 2.5 kHz heavy duty | |
---|
maximum transient current | 708 A 60 s per 10 min normal duty)716 A 60 s per 10 min heavy duty) | |
---|
line current | 491 A 400 V normal duty)389 A 400 V heavy duty) | |
---|
apparent power | 340 kVA 400 V normal duty)270 kVA 400 V heavy duty) | |
---|
maximum THDI | <5 % full load IEC 61000-3-12 | |
---|
short-circuit protection | Upstream 630 A gG fuse normal duty)Upstream 500 A gG fuse heavy duty)Internal 400 A 2 aR fuse | |
---|
energy efficiency ratio | 0,965 | |
---|
power dissipation in W | 13060 W, total normal duty)9890 W, total heavy duty)1560 W, control part normal duty)1140 W, control part heavy duty) | |
---|
volume of cooling air | 2320 m3/h power280 m3/h control | |
---|
prospective line Isc | 50 kA 100 ms | |
---|
electrical connection | Removable screw terminals 0.5...1.5 mm² controlM12 bar main supplyM12 bar motor | |
---|
motor recommanded cable cross section | 2 x 3 x 185 mm²)normal duty)3 x 3 x 120 mm²)normal duty)2 x 3 x 185 mm²)heavy duty)3 x 3 x 120 mm²)heavy duty) | |
---|
width | 1000 mm | |
---|
height | 2150 mm | |
---|
depth | 664 mm | |
---|
net weight | 700 kg | |
---|
number of preset speeds | 16 preset speeds | |
---|
communication port protocol | Modbus serialEthernet/IPModbus TCP | |
---|
option module | Slot A communication module EtherCATSlot A/slot B/slot C digital and analog I/O extension moduleSlot A/slot B/slot C output relay extension moduleSlot A communication module CANopen daisy chain RJ45Slot A communication module CANopen screw terminalsSlot A communication module CANopen SUB-D 9Slot A communication module DeviceNetSlot A communication module Profibus DP V1Slot A communication module ProfinetSlot B 512 V digital encoder interface moduleSlot B digital encoder interface moduleSlot B resolver encoder interface moduleSlot B analog encoder interface module | |
---|
safety function | STO (safe torque off) SIL 3 <= 100 ms | |
---|
motor slip compensation | AdjustableNot available in permanent magnet motor lawCan be suppressedAutomatic whatever the load | |
---|
acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 9000 sS, U or customized | |
---|
braking to standstill | By DC injection | |
---|
protection type | Motor thermal protectionMotor safe torque offMotor motor phase breakDrive thermal protectionDrive safe torque offDrive overheatingDrive overcurrent between output phases and earth)Drive overload output)Drive short-circuit protectionDrive motor phase breakDrive overvoltage DC bus)Drive line supply overvoltageDrive line supply undervoltageDrive line supply phase lossDrive overspeedDrive break on the control circuitDrive short-circuit protection semi-conductor fuse main supply)Drive fan monitoring | |
---|
frequency resolution | Display unit 0.1 HzAnalog input 0.012/50 Hz | |
---|
connector type | 2 RJ45 Ethernet IP/Modbus TCP on the control block1 RJ45 Modbus serial on the control block | |
---|
physical interface | 2-wire RS 485 Modbus serial | |
---|
transmission frame | RTU Modbus serial | |
---|
transmission rate | 10/100 Mbit/s Ethernet IP/Modbus TCP4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial | |
---|
exchange mode | Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP | |
---|
data format | 8 bits, configurable odd, even or no parity Modbus serial | |
---|
number of addresses | 1…247 Modbus serial | |
---|
method of access | Slave Modbus TCP | |
---|
analogue input number | 3 | |
---|
analogue input type | AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bitsAI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits | |
---|
discrete input number | 10 | |
---|
discrete input type | DI1...DI8 programmable, 24 V DC 30 V)3.5 kOhmDI7, DI8 programmable as pulse input 0…30 kHz, 24 V DCSTOA, STOB safe torque off, 24 V DC> 2.2 kOhm | |
---|
input compatibility | DI1...DI8 discrete input level 1 PLC EN/IEC 61131-2DI7, DI8 pulse input level 1 PLC IEC 65A-68STOA, STOB discrete input level 1 PLC EN/IEC 61131-2 | |
---|
discrete input logic | Positive logic (source) DI1...DI8), < 5 V, > 11 VNegative logic (sink) DI1...DI8), > 16 V, < 10 VPositive logic (source) DI7, DI8), < 0.6 V, > 2.5 VPositive logic (source) STOA, STOB), < 5 V, > 11 V | |
---|
analogue output number | 2 | |
---|
analogue output type | Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bitsSoftware-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits | |
---|
discrete output number | 2 | |
---|
discrete output type | Logic output DQ+ 0…1 kHz <= 30 V DC 100,0 mAProgrammable as pulse output DQ+ 0…30 kHz <= 30 V DC 20,0 mALogic output DQ- 0…1 kHz <= 30 V DC 100,0 mA | |
---|
sampling duration | 2 ms +/- 0.5 ms DI1...DI8) - discrete input5 ms +/- 1 ms DI7, DI8) - pulse input1 ms +/- 1 ms AI1, AI2, AI3) - analog input5 ms +/- 1 ms AQ1, AQ2) - analog output | |
---|
accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output | |
---|
linearity error | AI1, AI2, AI3 +/- 0.15 % of maximum value analog inputAQ1, AQ2 +/- 0.2 % analog output | |
---|
relay output number | 3 | |
---|
relay output type | Configurable relay logic R1 fault relay NO/NC 100000 cyclesConfigurable relay logic R2 sequence relay NO 1000000 cyclesConfigurable relay logic R3 sequence relay NO 1000000 cycles | |
---|
refresh time | Relay output R1, R2, R3)5 ms +/- 0.5 ms) | |
---|
minimum switching current | Relay output R1, R2, R3 5 mA 24 V DC | |
---|
maximum switching current | Relay output R1 resistive, cos phi = 1 3 A 250 V ACRelay output R1 resistive, cos phi = 1 3 A 30 V DCRelay output R1 inductive, cos phi = 0,4 7 ms 2 A 250 V ACRelay output R1 inductive, cos phi = 0,4 7 ms 2 A 30 V DCRelay output R2, R3 resistive, cos phi = 1 5 A 250 V ACRelay output R2, R3 resistive, cos phi = 1 5 A 30 V DCRelay output R2, R3 inductive, cos phi = 0,4 7 ms 2 A 250 V ACRelay output R2, R3 inductive, cos phi = 0,4 7 ms 2 A 30 V DC | |
---|
isolation | Between power and control terminals | |
---|
insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth | |
---|
operating position | Vertical +/- 10 degree | |
---|
marking | CE | |
---|