| product destination |  asynchronous motors synchronous motors |  | 
|---|
| assembly style |  In floor-standing enclosure compact version |  | 
|---|
| cable entry |  Bottom |  | 
|---|
| type of cooling |  Forced convection |  | 
|---|
| [Us] rated supply voltage |  380...415 V - 10...6 % |  | 
|---|
| supply frequency |  50...60 Hz +/- 5 % |  | 
|---|
| network number of phases |  3 phases |  | 
|---|
| overvoltage category |  III |  | 
|---|
| synchronous motor control profile |  Permanent magnet motor |  | 
|---|
| output voltage | <= power supply voltage |  | 
|---|
| permissible temporary current boost |  1.2 x In 60 s normal duty)1.5 x In 60 s heavy duty) |  | 
|---|
| nominal switching frequency |  2.5 kHz |  | 
|---|
| switching frequency |  2...8 kHz adjustable with derating factor |  | 
|---|
| speed drive output frequency |  0,1…500 Hz |  | 
|---|
| motor power kW |  710 kW normal duty560 kW heavy duty |  | 
|---|
| continuous output current |  1260 A 2.5 kHz normal duty1020 A 2.5 kHz heavy duty |  | 
|---|
| maximum transient current |  1512 A 60 s per 10 min normal duty)1530 A 60 s per 10 min heavy duty) |  | 
|---|
| line current |  1094 A 400 V normal duty)868 A 400 V heavy duty) |  | 
|---|
| apparent power |  758 kVA 400 V normal duty)601 kVA 400 V heavy duty) |  | 
|---|
| maximum THDI | <5 % full load IEC 61000-3-12 |  | 
|---|
| short-circuit protection |  Upstream 1600 A gG fuse normal duty)Upstream 1250 A gG fuse heavy duty)Internal 400 A 5 aR fuse |  | 
|---|
| energy efficiency ratio |  0,965 |  | 
|---|
| power dissipation in W |  28230 W, total normal duty)21850 W, total heavy duty)3230 W, control part normal duty)2450 W, control part heavy duty) |  | 
|---|
| volume of cooling air |  5800 m3/h power700 m3/h control |  | 
|---|
| prospective line Isc |  50 kA 100 ms |  | 
|---|
| electrical connection |  Removable screw terminals 0.5...1.5 mm² controlM12 bar main supplyM12 bar motor |  | 
|---|
| motor recommanded cable cross section |  5 x 3 x 150 mm²)heavy duty)5 x 3 x 185 mm²)normal duty) |  | 
|---|
| width |  2600 mm |  | 
|---|
| height |  2150 mm |  | 
|---|
| depth |  664 mm |  | 
|---|
| net weight |  1950 kg |  | 
|---|
| number of preset speeds |  16 preset speeds |  | 
|---|
| communication port protocol |  Modbus TCPEthernet/IPModbus serial |  | 
|---|
| option module |  Slot A communication module EtherCATSlot A/slot B/slot C digital and analog I/O extension moduleSlot A/slot B/slot C output relay extension moduleSlot A communication module CANopen daisy chain RJ45Slot A communication module CANopen screw terminalsSlot A communication module CANopen SUB-D 9Slot A communication module DeviceNetSlot A communication module Profibus DP V1Slot A communication module ProfinetSlot B 512 V digital encoder interface moduleSlot B digital encoder interface moduleSlot B resolver encoder interface moduleSlot B analog encoder interface module |  | 
|---|
| safety function |  STO (safe torque off) SIL 3 <= 100 ms |  | 
|---|
| motor slip compensation |  Automatic whatever the loadNot available in permanent magnet motor lawAdjustableCan be suppressed |  | 
|---|
| acceleration and deceleration ramps |  S, U or customizedLinear adjustable separately from 0.01 to 9000 s |  | 
|---|
| braking to standstill |  By DC injection |  | 
|---|
| protection type |  Motor thermal protectionMotor safe torque offMotor motor phase breakDrive thermal protectionDrive safe torque offDrive overheatingDrive overcurrent between output phases and earth)Drive overload output)Drive short-circuit protectionDrive motor phase breakDrive overvoltage DC bus)Drive line supply overvoltageDrive line supply undervoltageDrive line supply phase lossDrive overspeedDrive break on the control circuitDrive short-circuit protection semi-conductor fuse main supply)Drive fan monitoring |  | 
|---|
| frequency resolution |  Display unit 0.1 HzAnalog input 0.012/50 Hz |  | 
|---|
| connector type |  2 RJ45 Ethernet IP/Modbus TCP on the control block1 RJ45 Modbus serial on the control block |  | 
|---|
| physical interface |  2-wire RS 485 Modbus serial |  | 
|---|
| transmission frame |  RTU Modbus serial |  | 
|---|
| transmission rate |  10/100 Mbit/s Ethernet IP/Modbus TCP4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial |  | 
|---|
| exchange mode |  Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP |  | 
|---|
| data format |  8 bits, configurable odd, even or no parity Modbus serial |  | 
|---|
| number of addresses |  1…247 Modbus serial |  | 
|---|
| method of access |  Slave Modbus TCP |  | 
|---|
| analogue input number |  3 |  | 
|---|
| analogue input type |  AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bitsAI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits |  | 
|---|
| discrete input number |  10 |  | 
|---|
| discrete input type |  DI1...DI8 programmable, 24 V DC 30 V)3.5 kOhmDI7, DI8 programmable as pulse input 0…30 kHz, 24 V DCSTOA, STOB safe torque off, 24 V DC> 2.2 kOhm |  | 
|---|
| input compatibility |  DI1...DI8 discrete input level 1 PLC EN/IEC 61131-2DI7, DI8 pulse input level 1 PLC IEC 65A-68STOA, STOB discrete input level 1 PLC EN/IEC 61131-2 |  | 
|---|
| discrete input logic |  Positive logic (source) DI1...DI8), < 5 V, > 11 VNegative logic (sink) DI1...DI8), > 16 V, < 10 VPositive logic (source) DI7, DI8), < 0.6 V, > 2.5 VPositive logic (source) STOA, STOB), < 5 V, > 11 V |  | 
|---|
| analogue output number |  2 |  | 
|---|
| analogue output type |  Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bitsSoftware-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits |  | 
|---|
| discrete output number |  2 |  | 
|---|
| discrete output type |  Logic output DQ+ 0…1 kHz <= 30 V DC 100,0 mAProgrammable as pulse output DQ+ 0…30 kHz <= 30 V DC 20,0 mALogic output DQ- 0…1 kHz <= 30 V DC 100,0 mA |  | 
|---|
| sampling duration |  2 ms +/- 0.5 ms DI1...DI8) - discrete input5 ms +/- 1 ms DI7, DI8) - pulse input1 ms +/- 1 ms AI1, AI2, AI3) - analog input5 ms +/- 1 ms AQ1, AQ2) - analog output |  | 
|---|
| accuracy |  +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output |  | 
|---|
| linearity error |  AI1, AI2, AI3 +/- 0.15 % of maximum value analog inputAQ1, AQ2 +/- 0.2 % analog output |  | 
|---|
| relay output number |  3 |  | 
|---|
| relay output type |  Configurable relay logic R1 fault relay NO/NC 100000 cyclesConfigurable relay logic R2 sequence relay NO 1000000 cyclesConfigurable relay logic R3 sequence relay NO 1000000 cycles |  | 
|---|
| refresh time |  Relay output R1, R2, R3)5 ms +/- 0.5 ms) |  | 
|---|
| minimum switching current |  Relay output R1, R2, R3 5 mA 24 V DC |  | 
|---|
| maximum switching current |  Relay output R1 resistive, cos phi = 1 3 A 250 V ACRelay output R1 resistive, cos phi = 1 3 A 30 V DCRelay output R1 inductive, cos phi = 0,4 7 ms 2 A 250 V ACRelay output R1 inductive, cos phi = 0,4 7 ms 2 A 30 V DCRelay output R2, R3 resistive, cos phi = 1 5 A 250 V ACRelay output R2, R3 resistive, cos phi = 1 5 A 30 V DCRelay output R2, R3 inductive, cos phi = 0,4 7 ms 2 A 250 V ACRelay output R2, R3 inductive, cos phi = 0,4 7 ms 2 A 30 V DC |  | 
|---|
| isolation |  Between power and control terminals |  | 
|---|
| insulation resistance |  > 1 MOhm 500 V DC for 1 minute to earth |  | 
|---|
| operating position |  Vertical +/- 10 degree |  | 
|---|
| marking |  CE |  | 
|---|