apparent power | 52 kVA at 380 V | |
---|
prospective line Isc | 22 kA | |
---|
continuous output current | 79 A at 380 V79 A at 460 V | |
---|
maximum transient current | 86.9 A for 60 s | |
---|
speed drive output frequency | 0.5…200 Hz | |
---|
nominal switching frequency | 8 kHz | |
---|
switching frequency | 6...16 kHz adjustable8...16 kHz with derating factor | |
---|
speed range | 1…10 | |
---|
speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn | |
---|
torque accuracy | +/- 15 % | |
---|
transient overtorque | 120 % of nominal motor torque +/- 10 % for 60 s | |
---|
asynchronous motor control profile | Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)Flux vector control without sensor, standardVoltage/frequency ratio, 2 pointsVoltage/frequency ratio, 5 pointsVoltage/frequency ratio - Energy Saving, quadratic U/f | |
---|
regulation loop | Adjustable PI regulator | |
---|
motor slip compensation | Not available in voltage/frequency ratio motor controlAdjustableAutomatic whatever the load | |
---|
local signalling | 1 LED (red)DC bus energized: | |
---|
output voltage | <= power supply voltage | |
---|
isolation | Electrical between power and control | |
---|
type of cable | Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPRWithout mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVCWith UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC | |
---|
electrical connection | VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14L1/R, L2/S, L3/T: terminal 50 mm² / AWG 1/0 | |
---|
tightening torque | 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)24 N.m, 212 lb.in (L1/R, L2/S, L3/T) | |
---|
supply | Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protectionInternal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection | |
---|
analogue input number | 2 | |
---|
analogue input type | VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bitsVIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bitsVIB configurable PTC probe: 0...6 probes, impedance: 1500 OhmVIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits | |
---|
sampling duration | 2 ms +/- 0.5 ms F discrete2 ms +/- 0.5 ms R discrete2 ms +/- 0.5 ms RES discrete3.5 ms +/- 0.5 ms VIA analog22 ms +/- 0.5 ms VIB analog | |
---|
response time | FM 2 ms, tolerance +/- 0.5 ms for analog output(s)FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s) | |
---|
accuracy | +/- 0.6 % (VIA) for a temperature variation 60 °C+/- 0.6 % (VIB) for a temperature variation 60 °C+/- 1 % (FM) for a temperature variation 60 °C | |
---|
linearity error | VIA: +/- 0.15 % of maximum value for inputVIB: +/- 0.15 % of maximum value for inputFM: +/- 0.2 % for output | |
---|
analogue output number | 1 | |
---|
analogue output type | FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bitsFM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits | |
---|
discrete output number | 2 | |
---|
discrete output type | Configurable relay logic: (FLA, FLC) NO - 100000 cyclesConfigurable relay logic: (FLB, FLC) NC - 100000 cyclesConfigurable relay logic: (RY, RC) NO - 100000 cycles | |
---|
minimum switching current | 3 mA at 24 V DC for configurable relay logic | |
---|
maximum switching current | 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) | |
---|
discrete input type | F programmable 24 V DC, with level 1 PLC, impedance: 4700 OhmR programmable 24 V DC, with level 1 PLC, impedance: 4700 OhmRES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm | |
---|
discrete input logic | Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) | |
---|
acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 3200 sAutomatic based on the load | |
---|
braking to standstill | By DC injection | |
---|
protection type | Overheating protection: driveThermal power stage: driveShort-circuit between motor phases: driveInput phase breaks: driveOvercurrent between output phases and earth: driveOvervoltages on the DC bus: driveBreak on the control circuit: driveAgainst exceeding limit speed: driveLine supply overvoltage and undervoltage: driveLine supply undervoltage: driveAgainst input phase loss: driveThermal protection: motorMotor phase break: motorWith PTC probes: motor | |
---|
dielectric strength | 3535 V DC between earth and power terminals5092 V DC between control and power terminals | |
---|
insulation resistance | >= 1 mOhm 500 V DC for 1 minute | |
---|
frequency resolution | Display unit: 0.1 HzAnalog input: 0.024/50 Hz | |
---|
communication port protocol | LonWorksModbusAPOGEE FLNMETASYS N2BACnet | |
---|
connector type | 1 open style1 RJ45 | |
---|
physical interface | 2-wire RS 485 | |
---|
transmission frame | RTU | |
---|
transmission rate | 9600 bps or 19200 bps | |
---|
data format | 8 bits, 1 stop, odd even or no configurable parity | |
---|
type of polarization | No impedance | |
---|
number of addresses | 1…247 | |
---|
communication service | Read holding registers (03) 2 words maximumMonitoring inhibitableWrite single register (06)Write multiple registers (16) 2 words maximumRead device identification (43)Time out setting from 0.1 to 100 s | |
---|
option card | Communication card for LonWorks | |
---|
operating position | Vertical +/- 10 degree | |
---|
width | 284 mm | |
---|
height | 880 mm | |
---|
depth | 343 mm | |
---|
functionality | Mid | |
---|
specific application | HVAC | |
---|
IP degree of protection | IP55 | |
---|