EP MVS CB 2500A 65kA 3P EDO 240VAC ET5 drawout electrical circuit breaker

Tootekood: MVS25H3NW5L

Quick Overview

Saadavus: Tellimisel

6 131,93 € (ilma KM-ta)

Details

Main
range of product
EasyPact MVS
range
EasyPact
product name
MVS25H
device short name
MVS25H
product or component type
Circuit breaker
device application
Distribution
poles description
3P
protected poles description
3P 3d
network type
AC
breaking capacity code
H
suitability for isolation
Yes IEC 60947-2
utilisation category
Category B
trip unit name
ET5S
trip unit technology
Electronic
trip unit rating
2500 A
Complementary
network frequency
50/60 Hz
control type
Electrically operated
mounting mode
Drawout
mounting support
Rail
Base plate
connection position
Vertical
Horizontal
location of connection
Rear
[In] rated current
2500 A 40 °C
[Ui] rated insulation voltage
1000 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
12 kVIEC 60947-2
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
circuit breaker CT rating
2500 A
breaking capacity
65 kA Icu 220...440 V AC 50/60 Hz IEC 60947-2
[Ics] rated service breaking capacity
65 kA Ics)220...440 V AC 50/60 Hz IEC 60947-2
50 kA Ics)690 V AC 50/60 Hz IEC 60947-2
mechanical durability
20000 cycles with maintenance)IEC 60947-2
10000 cycles without maintenance)IEC 60947-2
electrical durability
Category B 5000 cycles 440 V AC 50/60 Hz without maintenance IEC 60947-2
Category B 2500 cycles 690 V AC 50/60 Hz without maintenance IEC 60947-2
connection pitch
115 mm without spreader
contact position indicator
Yes
[Icm] rated short-circuit making capacity
143 kA Icm) 220...440 V AC 50/60 Hz IEC 60947-2
[Icw] rated short-time withstand current
65 kA 1 s)220...440 V AC 50/60 Hz IEC 60947-2
50 kA 1 s)690 V AC 50/60 Hz IEC 60947-2
36 kA 3 s)440/690 V AC 50/60 Hz IEC 60947-2
trip unit protection functions
LSI
protection type
Short time short-circuit protection
Overload protection (long time)
Instantaneous short-circuit protection
fault indication
Overload
Short-circuit
Internal fault
long time pick-up adjustment type Ir
Adjustable 9 settings
long time pick-up adjustment range
0.4...1 x In
long time delay adjustment type
Adjustable 9 settings
[tr] long-time delay adjustment range
0,5…24 s 6 x Ir
short-time pick-up adjustment type Isd
Adjustable 9 settings
[Isd] short-time pick-up adjustment range
1.5...10 x Ir
short-time delay adjustment type
Adjustable 5 settings
[tsd] short-time delay adjustment range
100…400 ms
instantaneous pick-up adjustment type Ii
Adjustable 9 settings
instantaneous pick-up adjustment range
Off
2...15 x In
zone selective interlocking ZSI
With
current sensor rating range
1000/4000 A
maximum breaking time
25 ms
maximum closing response time
70 ms
height
439 mm
width
441 mm
depth
395 mm
net weight
90 kg
Environment
standards
IEC 60947-2
product certifications
IEC
GOST
CCS
CCC
IP degree of protection
IP40
pollution degree
4 IEC 60664-1
ambient air temperature for operation
-5…70 °C
ambient air temperature for storage
-40…85 °C without control unit
-25…85 °C with control unit
Offer Sustainability
ELi RoHS direktiiv
Elavhõbedavaba
Jah
RoHS eranditeave
Hiina EoHS regulatsioon
Hiina RoHS deklaratsioon
Toode ei kuulu Hiina RoHS sfääri. Ainedeklaratsioon teavitamiseks.
Keskkonnaalane avaldus
Ringlusprofiil
Contractual warranty
Garantii
18 months

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Quality
Value
Price