| range |  TeSys  |  | 
|---|
| product name |  TeSys D  |  | 
|---|
| product or component type |  Contactor  |  | 
|---|
| device short name |  LC1D  |  | 
|---|
| contactor application |  Motor controlResistive load  |  | 
|---|
| utilisation category |  AC-1AC-3AC-4  |  | 
|---|
| poles description |  3P  |  | 
|---|
| power pole contact composition |  3 NO  |  | 
|---|
| [Ue] rated operational voltage |  Power circuit <= 690 V AC 25...400 HzPower circuit <= 300 V DC  |  | 
|---|
| [Ie] rated operational current |  9 A 60 °C) <= 440 V AC AC-3 power circuit25 A 60 °C) <= 440 V AC AC-1 power circuit  |  | 
|---|
| motor power kW |  2,2 kW 220...230 V AC 50/60 Hz AC-3)4 kW 380...400 V AC 50/60 Hz AC-3)4 kW 415...440 V AC 50/60 Hz AC-3)5,5 kW 500 V AC 50/60 Hz AC-3)5,5 kW 660...690 V AC 50/60 Hz AC-3)2,2 kW 400 V AC 50/60 Hz AC-4)  |  | 
|---|
| motor power HP (UL / CSA) |  1 hp 230/240 V AC 50/60 Hz 1 phase2 hp 200/208 V AC 50/60 Hz 3 phases2 hp 230/240 V AC 50/60 Hz 3 phases5 hp 460/480 V AC 50/60 Hz 3 phases7,5 hp 575/600 V AC 50/60 Hz 3 phases0,33 hp 115 V AC 50/60 Hz 1 phase  |  | 
|---|
| control circuit type |  AC 50/60 Hz  |  | 
|---|
| [Uc] control circuit voltage |  230 V AC 50/60 Hz  |  | 
|---|
| auxiliary contact composition |  1 NO + 1 NC  |  | 
|---|
| [Uimp] rated impulse withstand voltage |  6 kV IEC 60947  |  | 
|---|
| overvoltage category |  III  |  | 
|---|
| [Ith] conventional free air thermal current |  25 A 60 °C power circuit10 A 60 °C signalling circuit  |  | 
|---|
| Irms rated making capacity |  250 A 440 V power circuit IEC 60947140 A AC signalling circuit IEC 60947-5-1250 A DC signalling circuit IEC 60947-5-1  |  | 
|---|
| rated breaking capacity |  250 A 440 V power circuit IEC 60947  |  | 
|---|
| [Icw] rated short-time withstand current |  105 A 40 °C - 10 s power circuit210 A 40 °C - 1 s power circuit30 A 40 °C - 10 min power circuit61 A 40 °C - 1 min power circuit100 A - 1 s signalling circuit120 A - 500 ms signalling circuit140 A - 100 ms signalling circuit  |  | 
|---|
| associated fuse rating |  10 A gG signalling circuit IEC 60947-5-125 A gG <= 690 V type 1 power circuit20 A gG <= 690 V type 2 power circuit  |  | 
|---|
| average impedance |  2,5 mOhm - Ith 25 A 50 Hz power circuit  |  | 
|---|
| [Ui] rated insulation voltage |  Power circuit 690 V IEC 60947-4-1Power circuit 600 V CSAPower circuit 600 V ULSignalling circuit 690 V IEC 60947-1Signalling circuit 600 V CSASignalling circuit 600 V UL  |  | 
|---|
| electrical durability |  0,6 Mcycles 25 A AC-1 <= 440 V2 Mcycles 9 A AC-3 <= 440 V  |  | 
|---|
| power dissipation per pole |  1,56 W AC-10,2 W AC-3  |  | 
|---|
| Front cover |  Without  |  | 
|---|
| mounting support |  PlateRail  |  | 
|---|
| standards |  CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508  |  | 
|---|
| product certifications |  RINACCCCSAULBVGOSTGLLROS (Lloyds register of shipping)DNV  |  | 
|---|
| connections - terminals |  Power circuit screw clamp terminals 1 1…4 mm²flexible without cable endPower circuit screw clamp terminals 2 1…4 mm²flexible without cable endPower circuit screw clamp terminals 1 1…4 mm²flexible with cable endPower circuit screw clamp terminals 2 1…2,5 mm²flexible with cable endPower circuit screw clamp terminals 1 1…4 mm²solid without cable endPower circuit screw clamp terminals 2 1…4 mm²solid without cable endControl circuit screw clamp terminals 1 1…4 mm²flexible without cable endControl circuit screw clamp terminals 2 1…4 mm²flexible without cable endControl circuit screw clamp terminals 1 1…4 mm²flexible with cable endControl circuit screw clamp terminals 2 1…2,5 mm²flexible with cable endControl circuit screw clamp terminals 1 1…4 mm²solid without cable endControl circuit screw clamp terminals 2 1…4 mm²solid without cable end  |  | 
|---|
| tightening torque |  Power circuit 1,7 N.m screw clamp terminals flat Ø 6 mmPower circuit 1,7 N.m screw clamp terminals Philips No 2Control circuit 1,7 N.m screw clamp terminals flat Ø 6 mmControl circuit 1,7 N.m screw clamp terminals Philips No 2  |  | 
|---|
| operating time |  12...22 ms closing4...19 ms opening  |  | 
|---|
| safety reliability level |  B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1  |  | 
|---|
| mechanical durability |  15 Mcycles  |  | 
|---|
| maximum operating rate |  3600 cyc/h 60 °C  |  | 
|---|